| Form |
|---|
| CSA of line conductor S | Minimum CSA of protective conductor if same material | Minimum CSA of protective conductor if different material |
|---|---|---|
| mm² | mm² | mm² |
| S ≤ 16 | S | k1/k2 x S |
| 16 < S ≤ 35 | 16 | k1/k2 x 16 |
| S > 35 | S/2 | k1/k2 x S/2 |
| Rating (A) | 3 | 6 | 10 | 16 | 20 | 25 | 32 | 40 | 50 | 63 | 80 | 100 | 125 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Zs (ohms) | 14.57 | 7.28 | 4.37 | 2.73 | 2.19 | 1.75 | 1.37 | 1.09 | 0.87 | 0.69 | 0.55 | 0.44 | 0.35 |
| Line conductor | Protective conductor | Copper |
|---|---|---|
| 1 | - | 18.10 |
| 1 | 1 | 36.20 |
| 1.5 | - | 12.10 |
| 1.5 | 1 | 30.20 |
| 1.5 | 1.5 | 24.20 |
| 2.5 | - | 7.41 |
| 2.5 | 1 | 25.51 |
| 2.5 | 1.5 | 19.51 |
| 2.5 | 2.5 | 14.82 |
| 4 | - | 4.61 |
| 4 | 1.5 | 16.71 |
| 4 | 2.5 | 12.02 |
| 4 | 4 | 9.22 |
| 6 | - | 3.08 |
| 6 | 2.5 | 10.49 |
| 6 | 4 | 7.69 |
| 6 | 6 | 6.16 |
| 10 | - | 1.83 |
| 10 | 4 | 6.44 |
| 10 | 6 | 4.91 |
| 10 | 10 | 3.66 |
| 16 | - | 1.15 |
| 16 | 6 | 4.23 |
| 16 | 10 | 2.98 |
| 16 | 16 | 2.30 |
| Conductor Installation | 70°C Thermoplastic (PVC) | 90°C Thermoplastic (PVC) | 90°C Thermosetting |
|---|---|---|---|
| Not incorporated in a cable and not bunched (NOTE 1) | 1.04 | 1.04 | 1.04 |
| Incorporated in a cable or bunched (NOTE 2) | 1.20 | 1.28 | 1.28 |
| Material of Conductor / Insulation of protective conductor or cable covering | 70°C Thermoplastic | 90°C Thermoplastic | 90°C Thermosetting |
|---|---|---|---|
| Copper | 143/133* | 143/133* | 176 |
| Aluminium | 95/88* | 95/88* | 116 |
| Steel | 52 | 52 | 64 |
| Assumed Initial Temperature | 30°C | 30°C | 30°C |
| Final Temperature | 160°C/140°C* | 160°C/140°C* | 250°C |
| Material of Conductor / Insulation material | 70°C Thermoplastic | 90°C Thermoplastic | 90°C Thermosetting |
|---|---|---|---|
| Copper | 115/103* | 100/86* | 143 |
| Aluminium | 76/68* | 66/57* | 94 |
| Assumed Initial Temperature | 70°C | 90°C | 90°C |
| Final Temperature | 160°C/140°C* | 160°C/140°C* | 250°C |